- 22 -
RECTIFIER FAIL INPUT
Pgm Description Std
101 Operation 2
0: Alarm (the engine stops and horn relay operates))
2: Warning (the horn relay operates)
3: No operation
102 Fault monitoring 2
0: Always
1: After holdoff timer
2: When mains present
103 Latching 1
0: Non latching
1: Latching
104 Contact type 0
0: Normally open
1: Normally closed
105 Switching 0
0: Battery negative
1: Battery positive
106 Response delay 1
0: No delay
1: Delayed (4sec)
EMERGENCY STOP INPUT
Pgm Description Std
107 Operation 0
0: Alarm (the engine stops and horn relay operates))
2: Warning (the horn relay operates)
3: No operation
108 Fault monitoring 0
0: Always
1: After holdoff timer
2: When mains present
109 Latching 0
0: Non latching
1: Latching
110 Contact type 0
0: Normally open
1: Normally closed
111 Switching 0
0: Battery negative
1: Battery positive
112 Response delay 0
0: No delay
1: Delayed (4sec)
SPARE-1 FAULT INPUT
Pgm Description Std
113 Operation 0
0: Alarm (the engine stops and horn relay operates))
2: Warning (the horn relay operates)
3: No operation
114 Fault monitoring 0
0: Always
1: After holdoff timer
2: When mains present
115 Latching 0
0: Non latching
1: Latching
116 Contact type 0
0: Normally open
1: Normally closed
117 Switching 0
0: Battery negative
1: Battery positive
118 Response delay 0
0: No delay
1: Delayed (4sec)