DKG-307 User Manual V-01.03
(14.02.2006)
- 11 -
6.2 Sender type Selection
The unit has the ability to adapt to any type of oil pressure and temperature senders. The
commonly used standard sender characteristics are recorded in memory and selectable from a list.
However non standard senders may also be used by entering their characteristics to the table.
Oil Pressure Sender Type Selection:
The oil pressure sender is selected using parameter P_019. The selectable sender types are:
0: The sender characteristics are defined in table using parameters P_131 to P_142.
1: VDO 0-7 bars (10-180 ohms)
2: VDO 0-10 bars (280-20 ohms)
3: DATCON 0-7 bars (240-33 ohms)
4: DATCON 0-10 bars (240-33 ohms)
5: DATCON 0-7 bars (0-90 ohms)
6: DATCON 0-10 bars (0-90 ohms)
7: DATCON 0-7 bars (75-10 ohms)
Temperature Sender Selection:
The temperature sender is selected using parameter P_020. The selectable sender types are:
0: The sender characteristics are defined in table using parameters P_143 to P_154.
1: VDO
2: DATCON DAH type
3: DATCON DAL type
6.3 Engine Heating Operation
Especially on engine without a body heater, or with a failing one, it may be desired that the genset
should not take the load before reaching a suitable temperature. The unit offers 2 different ways of engine
heating.
1. Timer controlled heating:
This operation mode is selected when the parameter P_037 is set to 0. In this mode, the engine will run
during parameter P_029, and then the genset will take the load.
2. Timer and temperature controlled heating:
This operation mode is selected when the parameter P_037 is set to 1. In this mode, at first the engine will
run during parameter P_029, then it will continue to run until the measured coolant temperature reaches
the limit defined in parameter P_022. When the requested temperature is reached, the load will be
transferred to the genset. This operation mode may be used as a backup to the engine body heater. If the
engine body is warm the heating will be skipped.